![LOVATO Electric DMED302MID 3 fázový elektroměr, 80A , MBUS LOVATO Electric DMED302MID 3 fázový elektroměr, 80A , MBUS](/var/shopelektro/storage/images/e-shop/modularni-pristroje/elektromery-a-multimetry/lovato-electric/elektromery/trifazove/trifazove-s-nebo-bez-nuloveho-vodice,-mid-certifikat/nerozsiritelne-trifazove-s-nulovym-vodicem,-certifikat-mid/lovato-electric-dmed302mid-3-fazovy-elektromer-80a-mbus/12857440-9-cze-CZ/lovato-electric-dmed302mid-3-fazovy-aD.jpg)
Elektroměr, funkce multimetru, třífázový, přímé měření 80A, certifikovaný MID, vestavěný M-BUS port
Hmotnost [g] | 377.9 |
---|---|
Počet kusů v balení | 1 |
Počet balení v objednávce | 1 |
Rozměry balení výrobků [mm] | 153X117X092 |
Objem [cm³] | 1646 |
Čárový kód [EAN13] | 8013975230640 |
Kód celního sazebníku | 90283019 |
Product designation | Three-phase energy meters | |||
Product type designation | DMED302MID | |||
Type | Three-phase + neutral | |||
DIN rail module number | 4 | |||
Auxiliary supply Us | ||||
Operational frequency | ||||
min | Hz | 50 | ||
Power consumption | ||||
Max | VA | 20 | ||
Power dissipation Max | W | 1.35 | ||
Measuring voltage inputs | ||||
Rated voltage (Ue) | ||||
phase-phase | VAC | 400 | ||
phase-neutral | VAC | 230 | ||
Operating voltage range | ||||
phase-phase | VAC | 323…456 | ||
phase-neutral | VAC | 187…264 | ||
Connection method | Direct | |||
Current | ||||
IEC maximum (Imax) | A | 63 | ||
IEC minimum (Imin) | A | 0.5 | ||
IEC rated (Iref-lb) | A | 10 | ||
IEC start (Ist) | mA | 40 | ||
Transition (Itr) | A | 1 | ||
Accuracy | ||||
Measurement conditions (T +23°C ±1°C / Rel. Humidity 45 ±15% R.H.) | ||||
active energy | Class B (EN/BS 50470-3) | |||
reactive energy | Class 2 (IEC/EN 62053-23) | |||
Output characteristics | ||||
LED Pulse rate | pulse/kWh | 1000 | ||
LED Pulse duration | ms | 30 | ||
Static output pulse rate | pulse/kWh | 1-10-100-1000 programmable | ||
Static output pulse duration | ms | 100 for 1-10-10 pulse; 60 for 1000 pulse | ||
Static output external voltage | VDC | 10…30 | ||
Static outputs Maximum current | mA | 50 | ||
Insulations | ||||
Rated insulation voltage Ui IEC/EN | V | 250 | ||
Rated impulse withstand voltage Uimp | kV | 6 | ||
Operating frequency withstand voltage | kV | 4 | ||
Mechanical features | ||||
Housing type | Polyamide | |||
Terminals type | Fixed | |||
Conductor cross section | ||||
min | mm² | 2.5 | ||
Max | mm² | 16 | ||
min | AWG | 16 | ||
Max | AWG | 6 | ||
Tightening torque (Max) | ||||
Nm | 2 | |||
lbin | 14 | |||
Fixing | Din rail | |||
Weight | g | 360 | ||
Ambient conditions | ||||
Temperature | ||||
Operating temperature | ||||
min | °C | -25 | ||
max | °C | +55 | ||
Storage temperature | ||||
min | °C | -25 | ||
max | °C | +70 | ||
Relative humidity | % | <80 | ||
Maximum Pollution degree | 2 | |||
Mechanical environment | Class M1 | |||
Magnetic environment | Class E1 | |||
ETIM classification | ||||
ETIM 8.0 | EC001506 - Kilowatt-hour meter |